Good price for Temperature Multi-Input Device for Cabinet Installation RD0-TI-Ex8.FF. PEPPERL+FUCHS RD0-TI-EX8.FF.ST Original new with good discount hot sale in stock with 1 year warranty
RD0-TI-EX8.FF.ST
The Temperature Multi-Input (TM-I) for DIN rail installation connects up to 8 analog inputs to the DCS via fieldbus. It is installed in a typically prewired field enclosure close to the sensors in the hazardous area. The TM-I is certified intrinsically safe and as associated apparatus: inputs are intrinsically safe even when the fieldbus connection is not. Analog inputs can be resistance temperature sensors with 2, 3, and 4 wires, measuring sensors, thermocouples, or millivolt signals. The TM-I communicates all data, configuration, and alarms via one fieldbus address and function blocks (8xAI or 1xMAI) to the DCS. For simplified configuration it supports the concentrator method: inputs can be configured all at once or individually. Fieldbus powers the sensors and the temperature interface itself, additional power or wiring is not required. Cold junction compensation for thermocouples is integrated. The TM-I detects and reports lead breakage and short circuit conditions.